Sign In | Join Free | My portofva.com |
|
Brand Name : Yushen
Model Number : SLNC-075Y
Certification : CCC, ISO, CQC
Place of Origin : China
MOQ : 1 set
Price : negotiable
Payment Terms : T/T
Supply Ability : 10 sets/day
Delivery Time : 1-2 weeks
Packaging Details : Reinforced Carton box with wooden tray
Key word : radiator ASHP
Compressor capacity : 25HP
Function : Heating and cooling
Fans : two
working conditions : -25C ~+45C
noise level : 62DBA
Primary School Building Heat Pumps Central Heating Indoor Radiator System
Main features
Technical data
Model | SLNC-075Ycode name.pdf | |||
Compressor capacity | 25HP | |||
Function | Heating and Cooling | |||
Electricity | 380V-3N-50Hz | |||
Working conditions | ℃ | -25~+45 | ||
Data | Heata | Nominal capacity | KW | 44.5 |
Input power | KW | 18.3 | ||
COP | / | 2.4 | ||
Heating IPLV(H) | 2.7 | |||
Coolb | Nominal capacity | KW | 62 | |
Input power | KW | 20.7 | ||
COP | / | 3 | ||
Cooling IPLV(C) | 2.7 | |||
A7W35c | KW/COP | 75.0/4.2 | ||
A2W35 | KW/COP | 62.5/3.20 | ||
A-7W35 | KW/COP | 50/2.9 | ||
A-15W55 | KW/COP | 45.5 /1.97 | ||
A-20W45 | KW/COP | 37.4/2.04 | ||
Max. running currency | A | 56 | ||
Compressor quantity | set | 2 | ||
Refrigerant/charging quantity kg | / | R22/15*2 | ||
Air blow type | / | Top | ||
Water pipe diameter | mm | 50 | ||
Rating flow | m³/h | 12.6 | ||
Water side pressure loss | kPa | ≤45 | ||
Noise level | dB(A) | 62 | ||
Overall dimensions(L×W×H) | mm | 2100×1100×2080 | ||
Weight | kg | 730 |
a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal heating capacity
b:Nominal refrigeration conditions: ambient dry bulb temperature 35℃, outlet water temperature 7℃, water flow 0.172 * nominal cooling capacity
c:A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃
YUSHEN Products
Working pricipal
heat exchanger through the air side (evaporator), absorption air inexhaustible low grade heat, while using the compressor work, into high grade heat release to the hot water side heat exchanger (condenser), resulting in high temperature water.
![]() |
Primary School Building Heat Pump Central Heating Indoor Radiator System Images |